Table 5. Potable Water System Troubleshooting Procedures.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
NO WATER PRESSURE
Step 1. Check main water
Open any closed main water
OR LOW WATER
valves.
valves.
PRESSURE
Open any closed valves at sinks,
Step 2. Check valves (1) at
urinal, and toilets.
sinks, urinal, and toilets.
Notify Unit Maintenance if the
Step 3. Check pressure gauge
water pressure does not read
(2). Ensure that water pressure
between 20 psi and 32 psi.
reads between 20 psi and 32 psi.
(CLS only)
Step 4. Check water pump.
Set water pump breaker (# 9/11)
Ensure that water pump circuit
to the ON position.
breaker (# 9/11) (3) is set to the
ON position.
Turn water pump supply switch to
Ensure water pump supply switch
the ON position.
(4) is set to ON position.
Ensure that water pump power
Plug water pump power cord into
cord (5) is plugged into the outlet.
the outlet.
(CLS only).
Ensure water pump has been
Prime pump.
primed.
Connect water supply to water
Step 5. Check main water supply
panel.
connection. For CL, see Force
Provider TM 10-5419-206-14 for
NOTE
water distribution system
For CL, get authorization from
information.
Force Provider water distribution
personnel prior to connecting to
water distribution leg.
Check all hoses for kinks and
Unkink all hoses and remove
obstructions.
obstructions.
Ensure that freshwater hose is
Connect freshwater hose. (CL
connected to top inlet connection.
only)
Notify Unit Maintenance.
0013 00-9