TM 10--3510--221--24
0249 00--3/4 blank
OVERLOAD RELAY REPLACEMENT -- Continued
0249 00
INSTALLATION
1. Insert new overload relay (12) into base adapter (10).
2. Connect wires to base adapter (10) and overload relay (12) as tagged.
3. Pull out on locking tab (9), then install base adapter (10) onto mounting rail (11).
4. Set reset control (13) to MO.
5. Adjust amperage control (14) to 29.0 for OL200 or 13.3 for OL300.
6. Place door (2) onto inverter enclosure (3), then secure by tightening eleven latches (1).
7. Use maintenance menu control outputs function (WP 0010 00) to verify correct operation of still condenser fan
M200 and thermal fluid pump M300.
END OF WORK PACKAGE