TM 10-3510-222-24
Table 2-2. UNIT LAUNDRY UNIT MAIN POWER TROUBLESHOOTING PROCEDURES
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
NO POWER TO COMPONENT CIRCUIT BREAKERS.
On electrical connector main power cable, check for continuity.
a.
Remove electrical power, refer to generator TM 5-6115-585-12.
b.
Remove main power cable from generator and power distribution panel.
NOTE
When testing for continuity between wires, disconnect one
end of wiring before testing. When testing for grounded
wires, disconnect both ends of wiring before testing.
c.
Using a multimeter, check for continuity between the following:
WIRE
CONNECTOR
(1)
Red
A
(2)
White
N
(3)
Blue
B
(4)
Green
G
(5)
Black
C
d.
If no continuity exists, notify Direct Support.
e.
If continuity exists, repair generator (TM 5-6115-585-12).
2-19