TM 10-3510-224-13&P
0028 00
Procedure 1: System Power Loss
INITIAL SETUP:
Equipment Condition
CSSL set-up, but not in operation
Materials/Parts
None
Maintenance Level
Direct Support
Personnel Required
One
IS POWER AVAILABLE AT MAIN BREAKERS?
USING A MULTIMETER SET TO READ AC
VOLTAGE, CHECK THE AVAILABILITY OF
POWER AT THE FOLLOWING POINTS IN
SEQUENCE:
1. AT THE PIGTAIL CABLE CONNECTION
TO THE POWER SOURCE.
2. AT THE CABLE CONNECTOR PLUG.
3. AT THE MAIN BREAKERS (CHECK FOR
PROPER CONNECTION OF THE VINYL
INSULATED SUPPLY WIRES TO THE MAIN
BREAKERS) (THE SEQUENCE SHOULD
BE BLACK ON THE TOP, RED AT THE
CENTER, AND BLUE AT THE BOTTOM
CONNECTOR.
4. IF NECESSARY, REMOVE POWER
ENTRY BOX FROM UTILITY WALL AND
ENSURE THE SUPPLY WIRES ARE
TIGHTLY CRIMPED TO THE CONTACT
PINS OF THE INPUT CONNECTORS.
5. REPLACE DEFECTIVE COMPONENTS
AND WIRING AS DESCRIBED IN WORK
PACKAGES 0027 00 TO 0039 00 AS
NECESSARY.
HAVE QUALIFIED PERSONNEL (MOS 51R,
52C, 52D, OR 52G) CONNECT 100 AMP
POWER CABLE PIGTAIL END TO POWER
SOURCE. SUPPLYING 100 AMP, 208
VOLT, 3 PHASE AC POWER (REFER TO
TM 9-6150-226-13) HAVE 100 AMP POWER
SUPPLY CABLES CONNECTED TO THE
CSSL POWER ENTRY PANEL
CONNECTORS ON THE UTILITY WALL.
(REFER TO WORK PACKAGE 0005) TURN
ON POWER AND SWITCH MAIN
BREAKERS (#10) IN BOTH POWER
DISTRIBUTION PANELS TO ON.
SWITCH COMPONENT BREAKERS TO ON AND
RESUME OPERATION.
IS CSSL CORRECTLY CONNECTED TO A
POWER SOURCE SUPPLYING 100 AMP, 208
VOLT, 3 PHASE, AC POWER ?
NO
YES
NO
YES
0028 00-2