TM 10-3510-226-23
UNIT MAINTENANCE
CONTAINERIZED BATCH LAUNDRY
CIRCUIT BREAKER
TEST, REPLACE
INITIAL SETUP
Tools
Personnel Required
Tool Kit, General Mechanics: Automotive (WP
Quartermaster and Chemical Equipment Repairer
63J (1)
Materials/Parts
Equipment Condition
CBL set up
TEST
Test Circuit Breakers
WARNING
This equipment operates at high voltages. Use extreme caution, observe all warnings,
and follow all safety procedures. Failure to observe safety precautions may result in
injury or death to personnel.
NOTE
Figures 1 and 3 illustrate the procedures on the main circuit breaker panel. Figure 2 and
4 illustrate the procedures on the dryer circuit breaker panel.
1. Switch all circuit breakers (Figures 1, 2, 3, 4, Item 1) to OFF.
2. Disconnect all power cables to the CBL.
3. Remove screws retaining the circuit breaker box cover (Figures 1, 2, Item 2) (Main Circuit Breaker
Panel only).
4. Remove the circuit breaker box cover (Figures 1, 2, Item 2) (Main Circuit Breaker Panel only).
5. Remove screws retaining the circuit breaker panel cover (Figure 1, Item 3).
6. Remove the circuit breaker panel cover (Figure 1, Item 3).