TM 10-3510-208-12
NOTE 2
LOAD TERMINALS ARE LOCATED BEHIND COVER
NOTE 1
WITH OUTPUT TERMINAL NUMBERS AS FOLLOWS
VOLTAGE SELECTION SWITCH (LOCATED BEHIND INSTRUMENT PANEL)
MUST BE IN THE 120/208V, 3 PH POSITION. (TM 5-6115-275-15 Fig. 2-6)
NOTE 3
GEN/EXT SELECTOR SWITCH TO MAKE SELECTION
FOR TYPE OF INPUT POWER.
Figure 2-8. Voltage selection.
7. Place governor control in GOVERN
position.
8. Pull OUT choke control, after engine
1. Place circuit breaker in OFF position.
starts slowly return to IN position.
2. Place remote-local switch in LOCAL
NOTE
position.
Before starting engine, check load terminals for
3. Place emergency stop-run switch in
correct output connection and voltage phase switch
NORMAL position.
position.
4. Turn voltage adjusting knob fully
9. Press the start-stop switch to the
counterclockwise.
START position, release after engine starts.
5. Set voltage selector switch to monitor
desired phase or line voltage.
6. Set current selector switch to monitor
desired current.
Change 3
2-12