TM 10-3510-208-12
essential in performing step 4. below. Minimum
(c) Manual Starting. Manually start the
voltage required for energizing K1 is 18 volts.
generator set using the following instructions and
1. Place emergency stop-run switch in
EMERGENCY RUN position.
NOTE
2. Place remote-local switch in LOCAL
Before starting perform step 1. of para (b) as listed
above.
position.
CAUTION
3. Pulll OUT choke control, after engine
starts slowly return choke control to the I N
Do not operate at idle speed. At idle speed,
position.
4. When engine oil pressure reaches
field voltage increases, thereby causing
operating pressure, place emergency stop-run
voltage regulator to operate at maximum
switch in NORMAL position and at the same time,
output. This causes overloading of power
press start-stop switch to START position and
transistor.
NOTE
release.
Manual start should not be attempted with a weak
battery or without a battery. Battery voltage is
2-14