TM 10-3510-220-10
2-8.
PREPARATION FOR USE. (CONT)
b. Generator.
WARNING
Do not operate the unit until the ground terminal stud
of the engine-generator set has been connected to a
suitable ground. Electrical faults in the engine-
generator set, load lines, or load equipment can cause
death by electrocution from contact with an
ungrounded system.
WARNING
Do not touch exhaust ducts while running or
immediately after shutdown, as severe burns may
result.
NOTE
The air compressor will operate when power is applied
to the laundry facility and the circuit breaker is on.
(1) Refer to TM 5-6115-585-12 for starting procedures for the generator
and start the generator.
(2) Turn on all circuit breakers at power distribution panel.
c. Air Compressor.
(1) Wait 2 minutes for pressure to build up inside air tank assembly and
check air tank gage (3, Figure 2-17) for an indication of 60 to 80 psi
(414 to 552 kPa).
(2) Open drain valve (2) to bleed condensation from air tank (1).
(3) Close drain valve.
(4) Turnoff generator. (Refer to TM 5-6115-585-12.)
(5) Listen for air leaks. If air leaks are found, report the problem to your
supervisor. If leaks are not found, restart and reset generator.
2-50