TM 10-3510-226-23
0019 00
REPLACE-CONTINUED
Replace the Phase Monitor Relay Fuse
WARNING
This equipment operates at high voltages. Use extreme caution, observe all warnings,
and follow all safety procedures. Failure to observe safety precautions may result in
injury or death to personnel.
1. Disconnect power.
2. Remove screws retaining power input panel interior cover, and remove cover.
3. Remove fuse cover (Figure 5, Item 2) from fuse (Figure 5, Item 3).
4. Remove fuse (Figure 5, Item 3) from fuse holder (Figure 5, Item 4).
5. Install replacement fuse (Figure 5, Item 3) into fuse holder (Figure 5, Item 4).
6. Install fuse cover (Figure 5, Item 2) onto replacement fuse (Figure 5, Item 3).
7. Install the power input panel interior cover and retain with screws.
8. Connect power and monitor for normal operation.