TM 10-3510-226-23
0061 00
TEST-CONTINUED
Test the Heat Contactors
WARNING
Ensure that all electrical power to the dryer is shut off and disconnected before
proceeding. The circuit breaker box should be locked by personnel following this
procedure. Serious injury or death can result from electrocution if proper safety
precautions are not observed.
1. Disconnect power.
2. Remove screws retaining the accessory box cover, and remove cover.
3. Locate the two heat contactors (Figure 3, Item 7).
WARNING
Use extreme caution when testing live electrical components. Serious injury or death can
result from electrocution if proper safety precautions are not observed.
4. Connect power and operate dryer.
5. Check for 210 VAC across primary terminals L1, L2, and L3 (Figure 3, Item 2). If no voltage is
present, refer to WP 0010 for dryer troubleshooting procedures.
NOTE
Allow the dryer to operate at high heat for at least 1 minute before testing.
6. Use a voltmeter to check for 210 VAC across secondary terminals T1, T2, and T3 (Figure 3, Item 3).
7. Repeat steps 4 and 5 for the remaining contactor.
8. Disconnect power.
9. Disconnect the white and red wires (Figure 3, Item 4) from the contactor control circuit, and use an
ohmmeter to test for 0 to 2 ohms across the two terminals. Replace an open contactor.
10. Reconnect the white and purple-and-white striped wires (Figure 3, Item 4) to the contactor control
circuit terminals.
11. Repeat steps 8 and 9 for the remaining contactor.
0061 00-5