CONDENSATE TEMPERATURE OR STILL PRESSURE HI
0052 00
THIS WORK PACKAGE COVERS:
Troubleshooting Condensate Temperature or Still Pressure Hi Fault
INITIAL SETUP:
Maintenance Level
Materials/Parts
Unit
Tools and Special Tools
Equipment Conditions
Tool Kit, General Mechanics (Item 1, WP 0272 00)
Power must be applied at main control
enclosure (WP 0010 00).
1. Use maintenance menu to turn on still condenser fan (WP 0010 00).
Does fan come on?
YES Go to step 2.
NO CONDENSER FAN DOES NOT TURN ON FAULT (WP 0064 00).
2. Position SW2 and SW1 to OFF.
3. Check for debris on screens covering still condenser heat exchangers.
Are screens clean?
YES Go to step 4.
NO Clean screens (TM 10--3510--221--10). Return to normal operation.
4. Remove screens from still condenser (TM 10--3510--221--10).
5. Check for debris or bent fins that would prevent air flow through cooling fins of heat exchangers.
Are cooling fins bent or blocked?
YES Straighten fins or remove debris (TM 10--3510--221--10). Return to normal operation.
NO Go to step 6.
6. Check for debris blocking still condenser fan guard.
Is debris block fan guard?
YES Clean fan guard. Return to normal operation.
NO Go to step 7.
7. Check for dirt buildup or damage to still condenser fan blades.
Are fan blades dirty or damaged?
YES Clean fan blades if dirty or replace if damaged (WP 0160 00). Return to normal operation.
NO Return to normal operation.
END OF WORK PACKAGE