TM 10--3510--221--24
0065 00--3/4 blank
DISTILLATE PUMP DOES NOT TURN ON -- Continued
0065 00
19. Check wiring and connection between distillate pump contactor terminal (A1) and SSR PCB3.
Is connection OK?
YES Go to step 20.
NO Repair as necessary.
20. Check wiring and connection between distillate pump contactor terminal (A2) and distillate pump overload
relay terminal (95).
Is connection OK?
YES Go to step 21.
NO Repair as necessary.
21. Check wiring and connection between distillate pump overload relay terminal (96) and TB2 terminal (N).
Is connection OK?
YES Replace overload relay (WP 0221 00).
NO Repair as necessary.
22. Check for >200 VAC across CB6 input terminals (L1 and L2), (L1 and L3), and (L2 and L3).
Is >200 VAC present?
YES Go to step 23.
NO Check wire connections between CB6 and TB1.
23. Check for >200 VAC across CB6 output terminals (T1 and T2), (T1 and T3), and (T2 and T3).
Is >200 VAC present?
YES Check wire connections between CB6 and distillate pump contactor.
NO Replace CB6 (WP 0218 00).
END OF WORK PACKAGE