PHASE MONITOR REPLACEMENT --
Continued
0225 00
INSTALLATION
1. Install new phase monitor (2) onto subpanel (5), then secure with two screws (3) and lock washers (4).
2. Slide covers (1) out of phase monitor (2).
3. Connect wires to phase monitor (2) as tagged.
4. Slide covers (1) into phase monitor (2).
5. Set LINE VOLTAGE adjustment (6) to 210 VAC.
6. Set % VOLTAGE UNBALANCE adjustment (7) to 5.
7. Set TRIP DELAY adjustment (8) to 11.
8. Turn handle (9) CW, then close door (10).
9. Secure door (10) to main control enclosure (11) by tightening eleven latches (12).
10. Position MAIN DISCONNECT switch (WP 0009 00, Figure 1, 1) to ON.
11. Position CONTROL POWER switch (3) to ON.
12. Verify CONTROL POWER lamp (4) is on.