TM 10--3510--221--24
0231 00--2
EMERGENCY STOP SWITCH REPLACEMENT --
Continued
0231 00
INSTALLATION
1. Remove nut (5) from new emergency stop switch (4).
2. Install emergency stop switch (4) onto door (6) then secure with nut (5).
3. Install new contact block (1) onto switch base (3).
4. Slide locking lever (2) over then insert switch base (3) onto emergency stop switch (4).
5. Connect wires to contact block (1) as tagged.
6. Turn handle (7) CW, then close door (6).
7. Secure door (6) to main control enclosure (8) by tightening eleven latches (9).
8. Rotate knob (10) CW to ensure emergency stop switch (1) is not engaged.
9. Position MAIN DISCONNECT switch (WP 0009 00, Figure 1, 1) to ON.
10. Position CONTROL POWER switch (3) to ON.
11. Wait for control system to complete self--test then press EMERGENCY STOP switch (5).
12. Verify display (WP 0009 00, Figure 2, 6) at operator panel A, reads:
SYSTEM SHUTDOWN
EMERGENCY STOP
13. Position CONTROL POWER switch (WP 0009 00, Figure 1, 3) to OFF.
14. Rotate and pull out on EMERGENCY STOP switch (5).
15. Position CONTROL POWER switch (3) to ON.
16. Wait for control system to complete self--test then verify display (WP 0009 00, Figure 2, 6) reads:
PRESS TO START
END OF WORK PACKAGE