TM 10-3510-222-10
Table 3-1. Troubleshooting - continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
13.
AIR COMPRESSOR FAILSTO START.
Step 1.
Check for electrical power.
a.
Open power distribution panel.
b.
Check to see if air compressor number 3 circuit breaker has tripped. If tripped, reset
circuit breaker.
c.
Close power distribution panel.
Step 2.
Check for tripped full voltage starter.
a.
Open power distribution panel door.
b.
Set air compressor number 3 circuit breaker to OFF.
c.
Open enclosure box above power distribution panel.
d.
Press full voltage starter manual reset.
e.
Close enclosure box above on power distribution panel.
f.
Set air compressor number 3 circuit breaker to ON.
g.
Close power distribution panel door.
h.
If air compressor fails to start, notify unit maintenance.
14.
AIR COMPRESSOR FAILS TO DELIVER AIR PRESSURE.
Check for air pressure leaking.
a.
On air tank, see if drain cock is open. If open, close drain cock.
b.
If no air pressure, turn off air compressor number 3 circuit breaker and notify unit
maintenance.
3-13