PROCEDURE 3 COVERS:
External Component Power Loss
INITIAL SETUP:
CSSL set up but not in operation
Maintenance Level
Materials/Parts
Direct Support
None
PERFORM TROUBLESHOOTING PROCEDURES
#1
IS THE EXTERNAL COMPONENT POWER
CABLE PROPERLY CONNECTED TO THE
CORRECT CSSL POWER ENTRY BOX
CONNECTOR (J3 OR J4) ?
CONNECT COMPONENT POWER SUPPLY CABLE
AS DESCRIBED IN WORK PACKAGE 0005 00
ARE COMPONENT OPERATING CONTROLS
PROPERLY SET OR ADJUSTED ?
SET AND ADJUST COMPONENT CONTROLS AS
NECESSARY. (REFER TO WORK PACKAGE 0005
00)
IS EXTERIOR CIRCUIT BREAKER IN THE ON
POSITION AND IS POWER AVAILABLE AT
THE BREAKER ?
USING A MULTIMETER SET TO MEASURE AC
VOLTAGE, CHECK THE AVAILABILITY OF
POWER AT THE COMPONENT BREAKER.
(REFER TO WORK PACKAGE 0031 00)
IF COMPONENT FAILS TO FUNCTION,
PROCEED AS FOLLOWS:
REMOVE THE REAR COVER OF THE POWER
ENTRY BOX AND CHECK THE J3 AND J4
CONNECTOR WIRES FOR SECURE
ATTACHMENT TO THE CONNECTOR. CHECK
FOR PROPER CONNECTION TO POWER
ENTRY BOX (REFER TO WIRING DIAGRAM)
REPLACE DEFECTIVE COMPONENTS AS
DESCRIBED IN WORK PACKAGES 0031 00
THROUGH 0043 00, AS APPLICABLE
NO
YES
PLACE EXTERIOR CIRCUIT BREAKER IN THE ON
POSITION.
DISTRIBUTION BOX #1 BREAKER #29 = GFCI
DISTRIBUTION BOX #2 BREAKER #3 = 60AMP
IF NO POWER IS AVAILABLE, REPLACE
BREAKER.
(REFER TO WORK PACKAGE 0031 00)
IS POWER AVAILABLE AT MAIN BREAKERS?
USING A MULTIMETER SET TO MEASURE AC
VOLTAGE, CHECK THE AVAILABILITY OF
POWER AT THE MAIN BREAKER OF BOTH
POWER DISTRIBUTION BOXES.
(REFER TO WORK PACKAGE 0031 00)
NO
NO
NO
YES
YES
YES
END OF WORK PACKAGE