TM 10-7360-226-13&P
0010 00
CONTAINERIZED KITCHEN (WITH TRAILER)
TROUBLESHOOTING PROCEDURES (ELECTRICAL SYSTEM)
Table 1. Troubleshooting Procedures (Electrical System) Continued
Malfunction
Test or Inspection
Corrective Action
Ensure that the generator
power control circuit breaker
(Power Entrance Panel) is shut
(pushed in)
Notify unit maintenance
GENERATOR POWER
Press the GENERATOR
AVAILABLE indicator is lit,
POWER pushbutton (Main
GENERATOR POWER indicator is
Control Panel)
not lit.
Notify unit maintenance
GENERATOR POWER
Check/reset the input power
AVAILABLE indicator is lit,
circuit breaker (#1 on Power
GENERATOR POWER indicator is
Distribution Panel).
lit
Notify unit maintenance
Generator will not
Check that the E-Stop (Main
Reset E-Stop
crank
Control Panel) is reset (pulled out)
Check that DC control power circuit
Reset circuit breaker
breaker CB1 (behind generator
control panel) is reset (pushed in)
Check that the E-Stop circuit
Reset circuit breaker
breaker (Power Entrance Panel) is
reset (pushed in)
Place switch in NORMAL
CRANK switch is in NORMAL
(behind generator access door
accessible from inside the
mechanical room)
Check generator battery
If loose or corroded, notify unit
connections (inside access doors
maintenance
on both sides of generator)
Generator cranks but
Place switch in NORMAL
does not start
CRANK switch is in NORMAL
(behind generator access door
accessible from inside the
mechanical room)
0010 00-2