TM 10--3510--221--24
0010 00--2
LAUNDRY ADVANCED SYSTEM
MAINTENANCE MENU OPERATION -- Continued
0010 00
B. EXAMINING INPUTS
NOTE
All analog and discrete inputs that can be monitored using this function are listed in Tables
1 and 2. These inputs can also be accessed while laundry operations are in progress using
the OTHER OPTIONS function on the WASH CYCLE menu (TM 10--3510--221--10).
1. Monitor display, it should read:
ANALOG INPUTS
EXAMINE INPUTS
DISCRETE INPUTS
RETURN
2. Press appropriate MENU SELECTION switch as follows:
a. Select ANALOG INPUTS to monitor status of analog inputs. Proceed to step 3.
b. Select DISCRETE INPUTS to monitor status of discrete inputs. Proceed to step 3.
c. Select RETURN to exit examine inputs menu and return to step A5.
3. Monitor display, it should read:
PREVIOUS INPUT
ANALOG INPUTS
NEXT INPUT
RETURN
LT100A=1.50 VDC= 0 GALS
or
PREVIOUS INPUT
DISCRETE INPUTS
NEXT INPUT
RETURN
ZS100A = ON
4. Press appropriate MENU SELECTION switch as follows:
a. Select PREVIOUS INPUT to monitor previous input.
b. Select NEXT INPUT to monitor next input.
c. Select RETURN to exit analog or discrete inputs menu and return to step 2.
TABLE 1. Analog Inputs Data.
SENSOR
FUNCTION
RANGE
VOLTAGE
LT100A
Wash Tank A Level
0--78 GALS
1.5 -- 5.05 VDC
LT100B
Wash Tank B Level
0--78 GALS
1.5 -- 5.05 VDC
LT101A
Rinse 1 Tank A Level
0--78 GALS
1.5 -- 5.05 VDC
LT101B
Rinse 1 Tank B Level
0--78 GALS
1.5 -- 5.05 VDC
LT102
Rinse 2 Tank Level
0--140 GALS
1.5 -- 3.11 VDC