TM 10--3510--221--24
0010 00--3
LAUNDRY ADVANCED SYSTEM
MAINTENANCE MENU OPERATION -- Continued
0010 00
TABLE 1. Analog Inputs Data -- Continued.
SENSOR
FUNCTION
RANGE
VOLTAGE
LT200
Still Level
0--15 INCHES
1.5 -- 5.56 VDC
LT201
Standpipe Level
0--25 INCHES
1.5 -- 8.27 VDC
PT200
Still Internal Pressure
0--5 PSIG
1.0 -- 9.0 VDC
PT300
Thermal Fluid Pump Inlet Pressure
VAC -- 15 PSIA
1.0 -- 6.0 VDC
PT301
Thermal Fluid Pump Outlet Pressure
0--100 PSIG
1.0 -- 6.0 VDC
PT302
Heater Thermal Fluid Outlet Pressure
0--100 PSIG
1.0 -- 6.0 VDC
PT500
Air Tank Storage Pressure
0--200 PSIG
1.0 -- 6.0 VDC
PT501
Product Air Pressure
0--200 PSIG
1.0 -- 6.0 VDC
TE100
Ambient Air
--58 -- 212 F
0 -- 10.0 VDC
TE101A
Dryer A Inlet Air Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE101B
Dryer B Inlet Air Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE102A
Dryer A Outlet Air Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE102B
Dryer A Outlet Air Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE103
Rinse 2 Tank Water Temperature
--58 -- 212 F
0 -- 10.0 VDC
TE200
Still Internal Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE201
Still Condenser Outlet Water Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE202
Rinse 2 Tank Inlet Water Temperature
--58 -- 392 F
0 -- 10.0 VDC
TE300
Heater Outlet Thermal Fluid Temperature
--58 -- 482 F
0 -- 10.0 VDC
VREFL
PCB1 Voltage Reference Lo
N/A
0.77 VDC
VREFH
PCB1 Voltage Reference Hi
N/A
9.22 VDC
TABLE 2. Discrete Inputs Data.
DEVICE
FUNCTION
STATUS
FP300
Flame Programmer Alarm Signal
OFF = Normal/ON = Fault Detected
FS100A
Detergent A Flow Switch
OFF = No or Low Flow/ON = Flow
FS100B
Detergent B Flow Switch
OFF = No or Low Flow/ON = Flow
FS200
Anti--Foam Flow Switch
OFF = No or Low Flow/ON = Flow
K100A
Drum A Inverter Fault Signal
OFF = Normal/ON = Fault
K100B
Drum B Inverter Fault Signal
OFF = Normal/ON = Fault
K104
Dryer Blowers A and B Inverter Fault Signal
OFF = Normal/ON = Fault