Table 1. Electrical Troubleshooting Procedures for Containerized Batch Laundry.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. No electrical power to
any equipment
WARNING
WARNING
The equipment being tested or
The equipment being tested or
corrected operates at high
corrected operates at high voltages
voltages and current that can
and current that can cause serious
cause serious injury or death.
injury or death.
Reconnect cables. If no power is
Step 1. Check all electrical cables
present, check power source.
(Figure 1, Item 1) for proper
connection. Ensure power source is
operating correctly.
Replace fuses as necessary.
Step 2. Check Phase Monitor Relay
fuses (Figure 2, Item 2) IAW WP 0019
Replace Phase Monitor Relay.
Step 3. Check Phase Monitor Relay
Inspect and test breaker IAW
Step 4. Check main circuit breaker
Replace if necessary.
If further corrective action is
required, notify direct support
maintenance.
1
1
Figure 1. No Electrical Power to any Equipment.