Table 1. Electrical Troubleshooting Procedures for Containerized Batch Laundry - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
3. No electrical power to
dryers.
WARNING
WARNING
The equipment being tested or
The equipment being tested or
corrected operates at high voltages
corrected operates at high
and current that can cause serious
voltages and current that can
injury or death.
cause serious injury or death.
Step 1. If both dryers are not receiving
Reconnect cables. If no power is
power, check all electrical cables
present, check power source.
(Figure 4, Item 1) for proper
connection. Ensure power source is
operating correctly.
Step 2. If only one dryer is not
Reconnect cable.
receiving electrical power, check
electrical cable (Figure 4, Item 1) for
proper connection.
Step 3. Inspect and test power input
Replace damaged power input
panel (Figure 4, Item 2) IAW WP 0018
receptacle.
Step 4. Check dryer circuit breaker
Reset if necessary. Inspect and
(Figure 4, Item 3).
test breaker IAW procedures in
necessary.
Step 5. Check Phase Monitor Relay
Replace fuses as necessary.
fuses (Figure 4, Item 4) IAW WP 0019
Step 6. Check Phase Monitor Relay
Replace Phase Monitor Relay.
If further corrective action is
required, notify direct support
maintenance.