TM 10--3510--221--10
0019 00--4
WATER RECYCLE SYSTEM TROUBLESHOOTING --
Continued
0019 00
STANDPIPE NOT EMPTYING -- Continued
5.
Slightly open petcock on distillate pump.
Is water coming out of petcock?
YES Tighten petcock. Go to step 6.
NO Notify Maintenance.
6.
Using EXAMINE INPUTS mode observe LT201 reading for approximately five minutes.
Does reading drop to 3 inches at least once?
YES Return to normal operation.
NO Go to step 7.
7.
Position CONTROL POWER switch (WP 0008 00, Figure 1, 3) to OFF.
WARNING
208 VAC electrical power is present in main control enclosure. Use extreme caution when working
inside. Never place hands or tools on exposed wire connections. Death on contact may result if per-
sonnel fail to observe this safety precaution.
8.
Open door on main control enclosure.
9.
Observe position of circuit breaker CB6 (11).
Is circuit breaker ON?
YES Notify Maintenance.
NO Go to step 10.
10. Position circuit breaker to ON then close and secure door.
11. Position CONTROL POWER switch (3) to ON.
12. At operator panel A use MENU SELECTION switch (Figure 2, 7) to select PRESS TO START.
13. Using EXAMINE INPUTS mode observe LT201 reading for approximately five minutes.
Does reading drop to 3 inches at least once?
YES Return to normal operation.
NO Notify Maintenance.