TM 10-3510-222-10
MALFUNCTION INDEX
MALFUNCTION
PAGE
1.
No Power To Component Circuit Breakers ................................ ................................ ................................ . 3-2
2.
Water Pump Fails To Start ................................ ................................ ................................ ....................... 3-3
3.
Water Pump Fails To Deliver Water ................................ ................................ ................................ .......... 3-3
4.
Dryer Fails To Start ................................ ................................ ................................ ................................ .. 3-4
5.
Dryer Fails To Dry Laundry ................................ ................................ ................................ ....................... 3-5
6.
Extractor Fails To Start ................................ ................................ ................................ .............................. 3-6
7.
Extractor Fails To Drain ................................ ................................ ................................ ............................ 3-7
8.
Washer Fails To Start In Automatic ................................ ................................ ................................ .......... 3-8
9.
Washer Fails To Start In Manual................................ ................................ ................................ ................ 3-9
10.
Washer Fails To Fill With Water In Automatic ................................ ................................ ......................... 3-10
11.
Washer Fails To Fill With Water In Manual................................ ................................ ............................... 3-11
12.
Washer Fails To Drain ................................ ................................ ................................ .............................. 3-12
13.
Air Compressor Fails To Start ................................ ................................ ................................ .................. 3-13
14.
Air Compressor Fails To Deliver Air Pressure ................................ ................................ ........................... 3-13
Table 3-1. Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
WARNING
Be sure to read all Warnings in front of manual before troubleshooting.
NOTE
Before you use the troubleshooting tables, be sure you have performed all applicable operating
checks and verified that a malfunction exists. When a corrective action is performed, verify that
the action has corrected the malfunction. All malfunction deferred to the next higher level of
maintenance must be reported according to the instructions given in DA PAM 738-750.
1.
NO POWER TO COMPONENT CIRCUIT BREAKERS.
Step 1.
On power distribution panel, check for electrical power.
a.
Remove electrical power. Refer to generator TM 5-6115-585-12.
b.
Open door on power distribution panel.
c.
See if number 1 main circuit breaker (60 amp) has tripped. If tripped, reset circuit breaker.
3-2