TM 10-7360-226-13&P
CONTAINERIZED KITCHEN (WITH TRAILER)
UNIT MAINTENANCE PROCEDURES
ELECTRICAL SYSTEM
THIS SECTION COVERS
Inspect, Test, Replace
INITIAL SETUP
CK set up for operation
External power disconnected, generator shut down
Maintenance Level
Unit
Tools and Special Tools
GENERAL
This procedure contains information and instructions for inspecting, testing and making repairs
to the CK electrical system. Refer to WP 0044 00 for repair parts information.
WARNING
Disconnect the external power cable and ensure generator power is OFF
before making repairs to the Power Entrance Panel, Power Distribution
Panel, or Main Control Panel.
INSPECT
Inspect the condition of each circuit breaker, ground, neutral, and 220V/115V connection at the
Power Entrance Panel, Power Distribution Panel, Main Control Panel and Appliance Control
Box. Inspect lighting fixtures for loose or damaged hardware, frayed power cords, and
damaged connectors.
TEST
Power Entrance Panel: Using a
multimeter, check the power voltage on
both sides of
the
applicable circuit breaker the OFF position and ON position. With External Power ON at the
Main Control Panel check the voltage at contactor CR2. If generator power is being used check
voltage at contactor CR1. Follow the circuit diagrams in WP 0054 00 to check connections.
Replace faulty component using the procedure in the following section.
Appliance Control Box: Using a
multimeter, check the voltage on
both sides of
the applicable
circuit breaker and switch assemblies in the OFF position and ON position. Follow the circuit
diagrams in WP 0054 00 to check connections. Replace faulty component using the procedure
in the following section.
0026 00-1
Change 1