3--PHASE CONTACTOR REPLACEMENT --
Continued
0220 00
INSTALLATION
1. Pull out on locking tab (4), then install new contactor (1) onto mounting rail (5).
2. Insert overload relay (2) into contactor (1), then secure by tightening three screw terminals (3).
3. Connect wires to contactor (1) and overload relay (2) as tagged.
4. Turn handle (6) CW, then close door (7).
5. Secure door (7) to main control enclosure (8) by tightening eleven latches (9).
6. Using maintenance menu control outputs function (WP 0010 00) verify correct operation as follows:
a. For contactor MC101A test operation of water pump M101A.
b. For contactor MC101B test operation of water pump M101B.
c. For contactor MC105 test operation of water supply pump M105.
d. For contactor MC201 test operation of distillate pump M201.
END OF WORK PACKAGE